PTC Heater Electronics (Retrofit)
Correction code 16014567 FRT 1.14 NOTE: Unless otherwise explicitly stated in the procedure, the correction code and FRT listed above reflect all of the work required to perform this procedure, including the linked procedures. Do not stack correction codes unless explicitly told to do so. NOTE: See Flat Rate Times to learn more about FRTs and how they are created. NOTE: See Personal Protection to make sure you are wearing proper PPE when performing the procedure below. NOTE: See Ergonomic Precautions for safe and healthy working practices.
Equipment:
- 1109531-00-B - PTC/AC Header Removal Tool
- 1126453-00-A - Tweezers
- 1453448-01-A - Kit Digital Multimeter Set EXTECH 335
- 1467483-00-B - M3/Y Penthouse Service Insulator Kit
- 1131071-00-A - DUMMY DISCONNECT, PYRO, SAFETY
- 1780974-00-A - HV TOOL KIT
- 1076927-00-A - HIOKI RM 3548
- 1076928-00-A - TEST PROBES - HIOKI 9461
Torque Specifications
| Description | Torque Value | Recommended Tools | Reuse/Replace | Notes |
|---|---|---|---|---|
| Nuts that secure the compressor/PTC fuse |
![]() 4.5 Nm (3.3 lbs-ft) |
|
Replace | 1104458-00-A |
|
Nut that secures the HV battery ancillary positive busbar Nut that attaches the negative AC harness to the negative HV battery DC link busbar |
![]() 4.5 Nm (3.3 lbs-ft) |
|
Reuse | |
| Bolts (x2) that secure the PCS output fuse |
![]() 4.5 Nm (3.3 lbs-ft) |
|
Replace | 1115833-00-B |
| Nuts (x2) that attach the AC negative harness to the transformer |
![]() 2.5 Nm (1.8 lbs-ft) |
|
Reuse | |
| Screw that secures the HV carrier assembly |
![]() 3 Nm (2.2 lbs-ft) |
|
Reuse | |
| M4 nut and bolt |
![]() 2.5 Nm (1.8 lbs-ft) |
|
Reuse |
Remove
- Remove the ancillary bay cover. See Cover - Ancillary Bay (Remove and Install).
- Remove the pyrotechnic disconnect and install the dummy disconnect. See Pyrotechnic Battery Disconnect (Remove and Replace).
-
Use bungee to secure the HVC (high
voltage controller) in an upwards position.
NoteWrap the bungee around the RH headrest.
-
Remove and discard the patch nuts (x2)
that secure the 700VDC 63A compressor fuse, and remove the fuse from the vehicle.
TIpUse of the following tool(s) is recommended:
- Insulated 8 mm socket
-
Remove and discard the patch nuts (x2)
that secure the 700VDC 63A PCS output fuse, and remove the fuse from the vehicle.
TIpUse of the following tool(s) is recommended:
- Insulated 8 mm socket
-
Remove the nut that secures the HV
battery ancillary positive busbar.
TIpUse of the following tool(s) is recommended:
- Insulated 8 mm socket
-
Remove the HV battery ancillary
positive busbar from the AWD busbar and distribution assembly.
-
Remove the nut that attaches the
negative AC harness to the negative HV battery DC link busbar.
TIpUse of the following tool(s) is recommended:
- Insulated 8 mm socket
-
Remove the nuts (x2) that attach the
AC negative harness to the transformer.
TIpUse of the following tool(s) is recommended:
- Insulated 7 mm socket
-
Disconnect the HV carrier
connector.
-
Remove the screw that secures the HV
carrier assembly.
TIpUse of the following tool(s) is recommended:
- Insulated Torx T20 bit
-
Disconnect the HV battery return tube
from the RH rear of the new HV battery (1x spring clip).
-
Disconnect the ancillary harness
connector from the RH rear of the new HV battery.
NoteRelease the red locking tab and rotate the lever arm to release.
-
Remove the HV carrier assembly (2x
tabs, 2x locating pins).
NoteInsert the 4-pole header assembly removal tool into the align tool slot with short portion of the internal connector. Verify the tool is fully seated. Squeeze the tool release tabs and remove the HV carrier assembly.
Install
-
Apply a 600v heat shrink sleeve to the
harness, and then connect 2 terminals together using an M4 nut and bolt.
2.5 Nm (1.8 lbs-ft)NoteThe nut is 8 mm and the bolt is T20.TIpUse of the following tool(s) is recommended:- Insulated Torx T20 bit
- Insulated 8 mm socket
-
Install the HV carrier assembly (2x
tabs, 2x locating pins).
-
Install the screw that secures the HV
carrier assembly.
3 Nm (2.2 lbs-ft)TIpUse of the following tool(s) is recommended:- Insulated Torx T20 bit
-
Connect the ancillary harness
connector to the RH rear of the HV battery.
NoteHold the connector level with the header and secure with even upward force. Rotate the lever arm and secure the locking tab. Verify that the latch is fully secured and not damaged.
-
Remove the plug and connect the HV
battery return tube to thye RH rear of the HV battery (1x spring clip).
NotePerform a push-pull-push test to make sure that the hose is fully secured.NoteCoolant loss greater than 1L requires vacuum fill.
-
Connect the HV carrier
connector.
-
Install the nut that attaches the
negative AC harness to the negative HV battery DC link busbar.
4.5 Nm (3.3 lbs-ft)TIpUse of the following tool(s) is recommended:- Insulated 8 mm socket
-
Perform Hioki resistance test at AC
harness to negative HV battery DC link busbar.
NoteThe acceptable value is 55 μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Install upside-down M5 nuts (x2) to
the ancillary tray as circled in the image.
-
Install the HV battery ancillary
positive busbar to the AWD busbar and distribution assembly.
-
Install the nut that secures the HV
battery ancillary positive busbar.
4.5 Nm (3.3 lbs-ft)TIpUse of the following tool(s) is recommended:- Insulated 8 mm socket
-
Perform Hioki resistance test at
ancillary positive busbar bracket to positive HV battery DC link busbar.
NoteThe acceptable value is 60μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Install new bolts (x2) that secure the
700VDC 63A PCS output fuse.
4.5 Nm (3.3 lbs-ft)NoteMark after torque.TIpUse of the following tool(s) is recommended:- Insulated 8 mm socket
-
Perform Hioki resistance test at 63A
PCS fuse input joint.
NoteThe acceptable value is 145μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Perform Hioki resistance test at 63A
PCS fuse output joint.
NoteThe acceptable value is 105μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Install new nuts (x2) that secure the
700VDC 63A compressor fuse.
4.5 Nm (3.3 lbs-ft)NoteMark after torque.TIpUse of the following tool(s) is recommended:- Insulated 8 mm socket
-
Perform Hioki resistance test at 63A
compressor fuse output joint.
NoteThe acceptable value is 105 μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Perform Hioki resistance test at 63A
compressor fuse input joint.
NoteThe acceptable value is 145μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Install new nuts (x2) to secure the
700VDC 63A PTC heater fuse.
4.5 Nm (3.3 lbs-ft)NoteMark after torque.TIpUse of the following tool(s) is recommended:- Insulated 8 mm socket
-
Perform Hioki resistance test at 63A
PTC heater fuse output joint.
NoteThe acceptable value is 105 μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Perform Hioki resistance test at 63A
PTC heater fuse input joint.
NoteThe acceptable value is 145 μΩ or less. Perform zero adjust to Hioki meter prior to testing.
-
Install the fuses access insulator (3x
clips).
- Remove the dummy disconnect and install the pyrotechnic disconnect. See Pyrotechnic Battery Disconnect (Remove and Replace).
- Install the ancillary bay cover. See Cover - Ancillary Bay (Remove and Install).