04/06/2024 18:03:22

Tab - Fuse 63A 700VDC (Remove and Replace)

Correction code 1630010302 FRT 0.84 NOTE: Unless otherwise explicitly stated in the procedure, the above correction code and FRT reflect all of the work required to perform this procedure, including the linked procedures. Do not stack correction codes unless explicitly told to do so. NOTE: See Flat Rate Times to learn more about FRTs and how they are created. To provide feedback on FRT values, email LaborTimeFeedback@tesla.com. NOTE: See Personal Protection to make sure wearing proper PPE when performing the below procedure.

  • 1057602-00-A Ratchet, 1/4" Sq Dr, HV Insulated
  • 1057604-00-A Skt, 1/4" Sq Dr, 8mm, HV Insulated
  • 1057606-00-A Skt, 1/4" Sq Dr, 13mm, HV Insulated
  • 1131071-00-A Dummy Disconnect, Pyro, Safety
  • 1108272-00-B Cap, Logic Conn, Inv, 3DU
  • 1076927-00-A Resistance meter, microohm, Hioki RM 3548
  • 1076927-00-A Resistance meter, microohm, Hioki RM 3548
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Remove all jewelry (watches, bracelets, rings, necklaces, earrings, ID tags, piercings, etc.) from your person, and all objects (keys, coins, pens, pencils, tools, fasteners, etc.) from your pockets before performing any procedure that exposes you to high voltage.
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
If corrective eyewear is necessary to safely perform any procedure, make sure that the eyewear is securely restrained to the head and cannot fall off.
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning

Only technicians who have been trained in High Voltage Awareness and have completed all required certification courses (if applicable) are permitted to perform this procedure. Proper personal protective equipment (PPE) and insulating HV gloves with a minimum rating of class 0 (1000V) must be worn at all times a high voltage cable, busbar, or fitting is handled. Refer to Tech Note TN-15-92-003, High Voltage Awareness Care Points for additional safety information.

Torque Specifications

Table 1. Torque Specifications: Tab - Fuse 63A 700VDC (Remove and Replace)
Description Torque Value Recommended Tools Reuse/Replace Notes
Nuts (x2) that attach the A/C compressor fuse to the ancillary bay bus
2.5 Nm (1.8 lbs-ft)
  • Insulated tools:
    • 8 mm socket
    • Ratchet/torque wrench
Replace

Remove

  1. Remove the ancillary bay cover. See Ancillary Bay Cover (Remove and Replace).
    Warning IconA warning icon, calling your attention to a possibly risky situation
    Warning
    HV insulating gloves and leather glove protectors must be worn throughout the remainder of this procedure. Do not remove gloves or protectors until otherwise noted.
  2. Remove the pyrotechnic battery disconnect. See Pyro Disconnect - HV Battery (Remove and Replace).
  3. Remove and discard the nuts (x2) that attach the A/C compressor fuse to the ancillary bay bus, and then remove the fuse.
    Tip: Use of the following tool(s) is recommended:
    • Insulated tools:
      • 8 mm socket
      • Ratchet/torque wrench
    Warning IconA warning icon, calling your attention to a possibly risky situation
    Warning
    The video(s) included in this procedure are meant as an overview for supplemental purposes only. Follow all of the steps listed in the procedure to avoid damage to components and/or personal injury.

Install

  1. Perform a zero adjust of the Hioki resistance meter in preparation to measure resistances later in this procedure.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    Warning
    HV insulating gloves and leather glove protectors must be worn throughout the remainder of this procedure. Do not remove gloves or protectors until otherwise noted.
  2. Install the A/C compressor fuse to the ancillary bay bus, and then install new nuts (x2) to attach the fuse to the bus.
    2.5 Nm (1.8 lbs-ft)
    Tip: Use of the following tool(s) is recommended:
    • Insulated tools:
      • 8 mm socket
      • Ratchet/torque wrench
  3. Use the Hioki resistance meter to measure the resistance at the HV joint of the A/C compressor fuse and the positive DC busbar.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    CAUTION
    Do not short the side of the probe tip to the edge of the fuse lug.
    Informational PurposesAn informational icon, calling your attention
    Note
    The maximum acceptable resistance is 0.145 mΩ (145 μΩ). There is too much resistance in the High Voltage joint. Remove the fastener, clean areas with isopropyl alcohol, install fastener back and test again
  4. Use the Hioki resistance meter to measure the resistance at the HV joint of the A/C compressor fuse and the electrical harness terminal.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    CAUTION
    Do not short the side of the probe tip to the edge of the nut's captive washer.
    Informational PurposesAn informational icon, calling your attention
    Note
    The maximum acceptable resistance is 0.105 mΩ (105 μΩ). There is too much resistance in the High Voltage joint. Remove the fastener, clean areas with isopropyl alcohol, install fastener back and test again
  5. Measure the voltage across the pyrotechninc battery disconnect mount points, and then install the pyrotechnic battery disconnect. See Pyro Disconnect - HV Battery (Remove and Replace).
  6. Install the ancillary bay cover. See Ancillary Bay Cover (Remove and Replace).
    Informational PurposesAn informational icon, calling your attention
    Note
    Before installing the ancillary bay cover, inspect the ancillary bay cover seal and confirm there is no visual damage. If the seal is torn and/or delaminated, replace the ancillary bay cover.