Anchoring Details for Ground- or Wall-mounting Powerwall 3 with Wall Bracket on Existing Approved Foundation

A6

Reference these anchoring details when mounting Powerwall 3 to the provided mounting bracket.

Wood Studs (spaced at 12 to 17 inches)

If anchoring directly into wood studs, use at least four (one in each corner) ¼ inch wood screws with washers, of sufficient length for at least 2-½ inch embedment into the studs.

Informational PurposesAn informational icon, calling your attention
Note
See Channel Strut (Unistrut) for stud spacing greater than 17 inches, up to 24 inches.

Wood Studs (spaced at 12 to 17 inches)

If anchoring to blocking between wood studs, use minimum 2 x 4 in blocks, end-nailed into studs with two 16d (89 x 4 mm) nails or toe-nailed into studs with four 8d (64 x 3 mm) nails. Use at least four (one in each corner) ¼ inch wood screws with washers, of sufficient length for at least 2-½ inch embedment into the blocking.

Informational PurposesAn informational icon, calling your attention
Note
See Channel Strut (Unistrut) for stud spacing greater than 17 inches, up to 24 inches.

Metal Studs (spaced at 12 to 17 inches)

If anchoring directly to metal studs, studs must be minimum 18 gauge. Use at least four (one in each corner) #14 (¼ inch) sheet metal screws with washers, of sufficient length to penetrate at least 3 threads beyond the stud.

If backing is needed between the studs, the backing must be minimum 18 gauge. Attach backing to metal studs with 12 gauge 3x3 inch angle clip or Simpson SFC2.25 clips with two #10 sheet metal screws in each leg.

Informational PurposesAn informational icon, calling your attention
Note
See Channel Strut (Unistrut) for stud spacing greater than 17 inches, up to 24 inches.

A7 - Anchoring Details for Ground- or Wall-mounting Powerwall 3 with Wall Bracket on Existing Approved Foundation

Concrete Masonry Unit Wall

Minimum strength must be 2000 PSI.

Use at least four (one in each corner, in any available anchor slot) 3/8 inch concrete anchors of sufficient length for the embedment listed below.

Anchors shall not be installed within 12 inches (305 mm) of wall edges or 1-½ inches (38 mm) of masonry block edges.

Solid Concrete Wall

Minimum strength must be 2500 PSI.

Use at least four (one in each corner, in any available anchor slot) 3/8 inch concrete anchors of sufficient length for at least 2-½ inch embedment into the wall.

A8 - Anchoring Details for Ground- or Wall-mounting Powerwall 3 with Wall Bracket on Existing Approved Foundation

Brick Wall

(Double and Single Layer of Brick Masonry)

Minimum strength must be 2500 PSI.

Use at least four (one in each corner, in any available anchor slot) ¼ inch masonry anchors of sufficient length for the embedment listed below.

  • Kwik Conn 2 (No ESR). Minimum 1-¾ inch (44.5 mm) embedment required

Brick installation is only permitted in seismic design category A or B, and where ESR anchors are not required. Ground mount only.

Maximum Wind Speed Mounting Location
145 mph Within 10 ft (3048 mm) of wall edge
165 mph Not within 10 ft (3048 mm) of wall edge
Informational PurposesAn informational icon, calling your attention
Note
Faux brick veneer is not a supported wall type for Powerwall installations.
Informational PurposesAn informational icon, calling your attention
Note
Fasteners shall not be installed in mortar joints.
Channel Strut (Unistrut)

Struts must be minimum 12 gauge, and either 1-5/8 inch or 7/8 inch.

If mounting on wood studs, attach each strut to at least two studs, using at least one ¼ inch wood screw with washer per stud, of sufficient length for at least 2-½ inch embedment into the studs.

If mounting on metal studs, attach each strut to at least three studs, using at least one #14 (¼ inch) sheet metal screw with washer per stud, of sufficient length to penetrate at least 3 threads beyond the studs.

Informational PurposesAn informational icon, calling your attention
Note
For either wood or metal studs, these requirements are per Powerwall (e.g. two studs per Powerwall on wood studs, or three studs per Powerwall on metal studs).

To attach the bracket to the struts, use at least four (one in each corner) 3/8 inch hex head screws with washers and strut nuts.

Channel strut shall have a maximum unsupported span of 24 inches (610 mm) and shall not be cantilevered.