Make AC Power Connections to Supply and Load / Generation Panels

In each of the following steps:
  • Strip the ends of the wires and insert into the corresponding Gateway 3 terminal lugs.
  • Using an appropriate torque tool, tighten the lugs according to the table on the following page.
  • Use copper or aluminum wire only.
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Always ensure all equipment is safely de-energized and locked out prior to working, to prevent risk of electric shock. To avoid shock hazard, never power on the system without a connection to Earth at the Gateway 3.
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Incorrect wiring of AC conductors presents a risk of electrical shock or damage to equipment. Before energizing the system, ensure all connections are made correctly according to the instructions in this document and in accordance with local wiring codes and regulations.

Refer to Gateway 3 Wiring Overview for all Gateway 3 wiring requirements and recommendations, including wire colors and gauges.

Refer to Gateway 3 Wiring Diagrams for additional example system wiring diagrams.