STEP 3: Wall-Mount Powerwall 3 Using Wall Bracket

  1. Using a drill and level, mount the Powerwall bracket to a wall capable of supporting the full weight of Powerwall 3. See Anchoring Details for Ground- or Wall-mounting Powerwall 3 with Wall Bracket on Existing Approved Foundation for additional details on the type and number of fasteners to use.
    Figure 1. Bracket Measurements Relative to Powerwall and Floor
    Warning IconA warning icon, calling your attention to a possibly risky situation
    Warning
    Only install fasteners in the (4) slots on the horizontal bracket segments. Do not install fasteners on the vertical (center) segment, as these are not structural mounting holes.
    Informational PurposesAn informational icon, calling your attention
    Note
    The following diagram provides measurements for positioning rear conduit entry holes relative to the Powerwall 3 bracket (the measurements are the same for both knockouts).
  2. Move the dolly toward the wall, positioning Powerwall so that the mounting cleats are just above the flanges on the bracket.
  3. Lower Powerwall until both the upper and lower sets of cleats engage the flanges on the bracket.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    CAUTION
    Confirm Powerwall 3 is fully seated on all four cleats before proceeding.
  4. If ground-mounting Powerwall, use an 11/16-inch (or 17 mm) wrench to adjust the leveling feet until Powerwall is level. The unit should be level within ± 2 degrees side-to-side and within ± 5 degrees front-to-back.
    Informational PurposesAn informational icon, calling your attention
    Note
    The top of each foot must be visible above the threaded boss; do not unscrew the foot so far that the top is no longer visible.