Gateway 3 Wiring Overview

Component Recommended Wire Color Wire Gauge 1 Tool Size Wire Strip Length Torque
A Supply Terminals Black, Red 6 AWG – 250 kcmil 5/16-inch hex 1 ¼-inch (32 mm) 275 in-lb, 23 ft-lb
B Backup Terminals Black, Red (1x) #4 AWG - 250 kcmil 3/8-inch hex 1 ¼-inch (32 mm) 250 in-lb, 21 ft-lb
(2x) #4 AWG - 4/0 stranded2
C Main Neutral Terminals White (1x) #4 AWG - 250 kcmil 3/8-inch hex 1 ¼-inch (32 mm) 250 in-lb, 21 ft-lb
(2x) #4 AWG - 4/0 stranded2, 3
D Load / Generation Neutral Terminals White See table in Gateway 3 Neutral Bar and Ground Bars
E Backup Terminals on Internal Panelboard Black, Red 6 AWG – 250 kcmil 5/16-inch hex 1 ¼-inch (32 mm) 275 in-lb, 23 ft-lb
F Main Ground Terminals Green or Bare 6 AWG – 2/0 3/16-inch hex ¾-inch (20 mm) 120 in-lb, 10 ft-lb
G Load/Generation Ground Terminals Green or Bare See table in Gateway 3 Neutral Bar and Ground Bars
H Internal Panelboard See Acceptable Circuit Breakers and Install Load / Generation Breakers on Internal Panelboard
I Communication connector See Gateway 3 Communication Wiring

1 Use copper or aluminum conductors rated to a minimum of 75°C.

2 Conductors must be the same size and material when terminating more than one conductor under these terminals.

3Double lugging is allowed only when conductors are paralleled to increase ampacity for a single circuit.

Warning IconA warning icon, calling your attention to a possibly risky situation
CAUTION
Do not modify the factory lug configuration.