Backup Gateway 2 Specifications
Performance Specifications
AC Voltage (Nominal) | 120/240 V |
Feed-In Type | Split Phase |
Grid Frequency | 60 Hz |
Current Rating | 200 A |
Maximum Input Short Circuit Current | 10 kA1 |
Overcurrent Protection Device | 100-200A; Service Entrance Rated1 |
Overvoltage Category | Category IV |
Internal Primary AC Meter | Revenue accurate (+/– 0.2%) |
Internal Auxiliary AC Meter | Revenue accurate (+/– 2%) |
1 When protected by Class J fuses, Backup Gateway 2 is suitable for use in circuits capable of delivering not more than 22 kA symmetrical amperes.
Mechanical Specifications
Dimensions | 26 x 16 x 6 inches (660 x 411 x 149 mm) |
Weight | 45 lb (20.4 kg) |
Mounting | Wall mount, Semi-flush mount |
Environmental Specifications
Operating Temperature | –4°F to 122°F (–20°C to 50°C) |
Operating Humidity (RH) | Up to 100%, condensing |
Maximum Elevation | 9843 ft (3000 m) |
Environment | Indoor and outdoor rated |
Enclosure Type | NEMA 3R |