Backup Gateway 2 Specifications

Performance Specifications

AC Voltage (Nominal) 120/240 V
Feed-In Type Split Phase
Grid Frequency 60 Hz
Current Rating 200 A
Maximum Input Short Circuit Current 10 kA1
Overcurrent Protection Device 100-200A; Service Entrance Rated1
Overvoltage Category Category IV
Internal Primary AC Meter Revenue accurate (+/– 0.2%)
Internal Auxiliary AC Meter Revenue accurate (+/– 2%)

1 When protected by Class J fuses, Backup Gateway 2 is suitable for use in circuits capable of delivering not more than 22 kA symmetrical amperes.

Mechanical Specifications

Dimensions 26 x 16 x 6 inches (660 x 411 x 149 mm)
Weight 45 lb (20.4 kg)
Mounting Wall mount, Semi-flush mount

Environmental Specifications

Operating Temperature –4°F to 122°F (–20°C to 50°C)
Operating Humidity (RH) Up to 100%, condensing
Maximum Elevation 9843 ft (3000 m)
Environment Indoor and outdoor rated
Enclosure Type NEMA 3R