Configuring Conductor Export Limits

Overview

The Powerwall system can be configured to limit Powerwall discharge power. When Conductor Export Limits are programmed, the Powerwall discharge power is dynamically adjusted based on the amperage measured by designated current transformers (CTs) and the programmed Conductor Limit amperage threshold.

Set Conductor Export Limits

Install CTs

  • Conductor CTs must be installed on conductors that are:
    • Between the grid connection and the Powerwalls.
    • At a location where the Powerwalls have control over current.
  • CTs should be oriented such that the label faces toward the grid.

Complete Commissioning

  1. In the Commissioning Wizard, assign the correct CTs to Conductor.
    Informational PurposesAn informational icon, calling your attention
    Note
    CTs can only be assigned one designation, meaning a CT cannot be both a Site and a Conductor CT.
    Informational PurposesAn informational icon, calling your attention
    Note
    See the Powerwall Commissioning Guide for instructions to connect to the TEG Wi-Fi network and enter the Commissioning Wizard.
  2. Enter the amperage for the Conductor Limit on the Settings page.

At the conclusion of the commissioning process, a summary of the settings will be displayed.