Install Optional Remote Disable Switch

Informational PurposesAn informational icon, calling your attention
Note
This section provides guidelines on a system functionality. Please consult your local AHJ or Utility before use.

The Backup Gateway 2 can be wired to include an external Remote Disable switch that simultaneously commands all Powerwalls to become idle and enter a safe mode.

Installation Instructions

The Remote Disable switch is wired through a low voltage, 12 V DC, control circuit connected to the Gateway AUX port.

Figure 1. Wiring a Remote Disable Switch to the Backup Gateway AUX Port
  1. Remove the factory-installed jumper from pins 1 and 2 of the 5-position “AUX” connector inside the Gateway 2. See Appendix B: Wiring Reference for a diagram of the connector location.
  2. Using minimum 24 AWG conductors (maximum 16 AWG), with wiring methods according to code, connect pins 1 and 2 (labeled “SDO” and “SDI”) to a suitable disconnect switch.
  3. Confirm that all Powerwalls cease operation when the switch is open.

Operation

Initiate Remote Disable Turn the switch to the OFF (open) position
All Powerwalls will go to idle. This behavior is the same whether the AC utility grid is present or not.
Resume Powerwall Operation Turn the Switch to the ON (closed) position
AC Grid Present AC grid not present (Off-grid or AC grid is down)
Normal system operation will resume shortly Powerwall operation will only resume when the grid is back or a 12V jump start is provided to the Gateway

Guidelines for Remote Disable Switch Selection and Installation

  • Must be Listed or Recognized as "Emergency Stop Button", "Emergency Stop Device", "Emergency Stop Unit"
  • Must be lockable in the OFF/open position when necessary to comply with AHJ requirements
  • Must have a clear indication of ON/OFF position
  • Must be outdoor rated (NEMA 3R or higher)
  • Should be installed externally in a readily accessible location preferably near utility meter
  • The maximum low voltage wire run from switch to Gateway should not exceed 150 feet (45 m)
  • Should observe 12V, 0.1 A ratings