Backup Gateway 2 Communication Wiring

Table 1. Backup Gateway Communication Wiring
Terminal Name Recommended Wire Color Wire Gauge
1 12V + (Logic +) Brown 18 - 16 AWG (0.8 - 1.5 mm2)
2 GND (Earth) White 18 - 16 AWG (0.8 - 1.5 mm2)
3 CN + (CAN HI) Blue 24 – 16 AWG (0.2 – 1.5 mm2)
4 CN – (CAN LO) Yellow 24 – 16 AWG (0.2 – 1.5 mm2)
Table 2. Aux Wiring
Terminal Name Recommended Wire Color Wire Gauge
1 Remote Disable (OUT) - 24 – 16 AWG (0.2 - 1.5 mm2)
2 Remote Disable (IN) - 24 – 16 AWG (0.2 - 1.5 mm2)
3 Generator / Load Control (+) Red 18 – 16 AWG (0.8 - 1.5 mm2)
4 Generator / Load Control (-) Black 18 – 16 AWG (0.8 - 1.5 mm2)
5 Interlock pin - 24 – 16 AWG (0.2 - 1.5 mm2)
Table 3. External Meter Communication Wiring
Terminal Name Recommended Wire Color Wire Gauge
1 GND (Earth) / Shield - 24 – 16 AWG (0.2 - 1.5 mm2)
2 RS485 HI #1 Red 24 – 16 AWG (0.2 - 1.5 mm2)
3 RS485 LO #1 Black 24 – 16 AWG (0.2 - 1.5 mm2)
4 GND (Earth) / Shield - 24 – 16 AWG (0.2 - 1.5 mm2)
5 RS485 HI #2 Red 24 – 16 AWG (0.2 - 1.5 mm2)
6 RS485 LO #2 Black 24 – 16 AWG (0.2 - 1.5 mm2)
Table 4. Jump Start Wiring
Terminal Name Recommended Wire Color Wire Gauge
1 12V Red 24 – 16 AWG (0.2 - 1.5 mm2)
2 GND Black 24 – 16 AWG (0.2 - 1.5 mm2)