Inverter settings must be configured in advance by Tesla. Talk to your Tesla representative if
any of the default settings should be modified. The defaults for the inverter follow
each region's grid code.
Response to Abnormal Frequencies
requirements for abnormal operating performance Category II & Category
III
Note
Any changes to the set points
require approval from the local AHJ.
Shall Trip Category II & III
Shall Trip Function
Default
Settings
Ranges of
Allowable Settings
Frequency
(Hz)
Clearing Time
(s)
Frequency
(Hz)
Clearing Time
(s)
OF2
62.0
0.16
61.8-66.0
0.16-1000.0
OF1
61.2
300.0
61.0-66.0
180.0-1000.0
UF1
58.5
300.0
50.0-59.0
180.0-1000.0
UF2
56.5
0.16
50.0-57.0
0.16-1000.0
Response to Abnormal Voltage
requirements for abnormal operating performance Category II & Category
III
Shall Trip Category II
Shall Trip Function
Default
Settings
Ranges of
Allowable Settings
Voltage (p.u.
of Nominal Voltage)
Clearing Time
(s)
Voltage (p.u.
of Nominal Voltage)
Clearing Time
(s)
OV2
1.20
0.16
Fixed at 1.2
Fixed at 0.16
OV1
1.10
2
1.10-1.20
1.0-13.0
UV1
0.70
10
0.0-0.88
2.0-21.0
UV2
0.45
0.16
0.0-0.50
0.16-2.0
Shall Trip Category III
Shall Trip Function
Default
Settings
Ranges of
Allowable Settings
Voltage (p.u.
of Nominal Voltage)
Clearing Time
(s)
Voltage (p.u.
of Nominal Voltage)
Clearing Time
(s)
OV2
1.20
0.16
Fixed at 1.2
Fixed at 0.16
OV1
1.10
13.0
1.10-1.20
1.0-13.0
UV1
0.88
21.0
0.0-0.88
21.0-50.0
UV2
0.50
2.0
0.0-0.50
2.0-21.0
Accuracy
Trip
Setting
Accuracy
Voltage
+/- 1% of nominal voltage
Frequency
+/- 0.01 Hz
Reconnection Time
1% of set point
Trip Time
0.032 s for <5 s 1% of set point for >5 s
Active Power
+/- 5% of rated apparent power
Reactive Power
+/- 5% of rated apparent power
Volt Watt
Capabilities
Table 1. IEEE 1547-2018
Capabilities
Voltage-Active Power Parameters
Default Values (p.u)
Range (p.u)
V1
1.06Vn
1.05-1.09
P1
1.0
1
V2
1.1Vn
1.1
P2
0
0
P’2
0
0 - -1
Response Time
10s
0.5-90
Table 2. UL 1741SA Capabilities
Description
240V (Split Phase)
208V
Output power rating (W)
5000
4500
AC voltage range with function enabled (Vac)
247.2 - 288
214.24 – 249.6
Nominal AC voltage (Vac)
240
208
Manufacturer's stated output power accuracy (%)
±5
±5
Manufacturer's stated time accuracy (sec)
0.1sec
0.1sec
Settling time (sec)
0.5 to 90
0.5 to 90
Frequency Watt
Capabilities
Table 3. IEEE 1547-2018
Capabilities
Parameters
Category II
Category III
dbUF(Hz)
0.036
0-1
dbOF(Hz)
0.036
0.017-1.0
KOF, kUF
0.05
0.02-0.07
Tr(s)
5
0.2-10
Table 4. UL 1741SA Capabilities
Description
240V (Split Phase)
208V
Output power rating (W)
5000
4500
Settling time (sec)
0.2 to 10
0.2 to 10
Watt-Var
Capabilities
Active Power -Reactive Power Parameters
Default Values (p.u)
Range (p.u)
P3
1.0
1.0
P2
0.5
0.5
P1
0
0
P’1
0
0
P’2
-0.5
-0.5
P’3
-1.0
-1.0
Q3
-0.44
0.25-0.44
Q2
0
0-0.44
Q1
0
0-0.22
Q’1
0
0- -0.22
Q’2
0
0- -0.44
Q’3
0.44
-0.25- -0.44
Volt-Var
Capabilities
Table 5. IEEE 1547-2018
Capabilities
Voltage -Reactive Power Parameters
Default Values
Range p.u
VRef
Vn
0.95-1.05
V2
0.98Vn
0.93-1.04
Q2
0
0.5- -0.5
V3
1.02Vn
0.96-1.07
Q3
0
0.5- -0.5
V1
0.92Vn
0.88-1
Q1
0.44
1- -1
V4
1.08Vn
1-1.1
Q4
-0.44
1 - -1
Table 6. UL 1741SA Capabilities
Description
Value (240V Split Phase)
Value (208V)
Apparent power rating (VA)
5800
5200
Output power rating (W)
5000
4500
Nominal AC EPS voltage (V)
240
208
AC EPS voltage range with function enabled (Vac)
196.8-283.2
170.56-245.44
Max rated reactive Power (capacitive, overexcited) (VAr)
2900
2633
Max rated reactive Power (inductive, underexcited) (VAr)