Mount Powerwall on the Bracket
- Switch off Powerwall.
- Remove the left side cover from Powerwall.
-
Prepare Powerwall for side or
back cable entry:
- Using lift equipment, position Powerwall close to the wall and adjust the height of Powerwall until its mounting cleats are just above the flanges on the bracket.
- Lower Powerwall until the top cleat engages the top flange on the bracket and the bottom cleat aligns with the bottom flange.
- With both cleats engaged, lower Powerwall onto the bracket. An audible click will be heard when the cleats are seated in the bracket and the locking mechanism at the center of the top flange clicks into place.
- If floor-mounting Powerwall, use shims to ensure that Powerwall is level. The unit should be level within +/– 2 degrees side-to-side and within +/– 5 degrees front-to-back.
-
If wall-mounting Powerwall,
remove the feet from the unit.
NoteStep 8 applies only to updated versions of Powerwall (see Powerwall Identification).