Configure Gateway Primary (Meter X)
![](GUID-DDCCEEA7-103C-4DA6-97DC-AB27168B83A7-online-en-US.png)
Meter X has a CT for each conductor, with the following voltage references:
- CT 1: L1
- CT 2: L2
- For each CT, select the appropriate
location representing what it is measuring:NoteMeter X CTs can only be configured as a single location, e.g. all CTs are Site.
- Site: Used when CTs are installed on conductors (both L1 and L2) to measure Site.
- Conductor: Used when
CTs are installed (on both L1 and L2 conductors) to measure conductors being
controlled by Conductor Limits.
- Set the Conductor Limit in the Advanced Settings menu.
- None: Used when the Meter X CTs are not being used.
NoteIf any of the CT readings are inverted and it has been confirmed that they are oriented correctly, select the Flip check box to correct the reading. - Review the vitals for each CT
(voltage, current, and power factor) to confirm they have been installed and
configured correctly. NoteThe live power flow and current readings are available for each CT in real time, as well as an overview of all meters and CT settings, in the Metering tab.