Appendix G: Installations with Multiple Powerwall 3 Units

Maximum Number of Powerwall 3 Units Up to (4X)Powerwall 3 units
Informational PurposesAn informational icon, calling your attention
Note
The maximum number of Powerwall 3 units per installation may vary by market.
Overcurrent Protection Devices Each Powerwall 3 requires its own 60 A circuit breaker
Site Leader The Powerwall 3 connected to the Backup Switch is designated as the Leader Powerwall 3
Informational PurposesAn informational icon, calling your attention
Note
The system is commissioned by connecting to the Leader Powerwall 3.
Follower Unit Any Powerwall 3not connected to the Backup Switch is designated as a Follower unit
Leader to Follower Communication Ethernet (see Prepare Ethernet Wiring with RJ45 Connectors)
Internet Connection for Multiple Units


                Option 1: The Leader Powerwall 3 is connected to customer router over Wi-Fi
Option 2: Either the first or last Powerwall 3 (can be Leader or Follower) in the chain is connected to customer router via Ethernet

Informational PurposesAn informational icon, calling your attention
Note
Only connect the router to a Powerwall 3 at either end of the chain; do not connect it in the middle of the chain (see Connecting Powerwall 3 Units via Ethernet for example diagrams).
Allowable Mounting Configuration Side-by-side (front-to-back stacking is not supported for multiple Powerwall 3 units)
Maximum Wire Length Between Units See Plan Cable Length Between Components
Splitting PV Production Between Multiple Units Split PV production [strings] equally between the Powerwall 3 units
System Shutdown Switch with Multiple Units Where a single System Shutdown Switch is required, each unit must be wired to a dedicated switching pole of the switch. Ensure the installed System Shutdown Switch has enough switching poles for the number of units installed. See STEP 8: Install System Shutdown Switch Where Required for switch requirements and additional information
Figure 1. Multi-Powerwall 3 System with Backup Gateway 2

System Shutdown Switch with Multiple Powerwall 3 Units

Where a System Shutdown Switch is required, each Powerwall 3 must be wired to a dedicated switching pole of the switch. Ensure the installed System Shutdown Switch has enough switching poles for the number of units installed.

Figure 2. 4-Pole System Shutdown Switch with Four Powerwall 3 Units

In the event multiple System Shutdown Switches are required to accommodate the number of Powerwall 3 units installed, simply install multiple switches, placing them physically near each other and following all local codes and requirements.

Figure 3. Two 3-Pole System Shutdown Switches with Four Powerwall 3 Units

Connecting Powerwall 3 Units via Ethernet

All Powerwall 3 units must be connected via Ethernet. The units can be connected in any order, so long as each unit is connected to at least one other unit.

Figure 4. Example 1: Leader Powerwall 3 at Start of Chain, Connected to Customer Router via Wi-Fi
Figure 5. Example 2: Leader Powerwall 3 at Start of Chain, Connected to Customer Router via Ethernet
Figure 6. Example 3: Leader Powerwall 3 in Middle of Chain, Connected to Customer Router via Wi-Fi
Informational PurposesAn informational icon, calling your attention
Note
If connecting the system to the customer router via Ethernet, connect the router to either the first or last Powerwall 3 in the chain. Do NOT connect the router in the middle of the chain.

Commissioning Multi-Powerwall 3 Systems

For instructions to commission a multi-Powerwall 3 system, as well as for troubleshooting steps for common issues, see the Powerwall 3 Device Setup Guide.