Configure Gateway Primary (Meter X)

Figure 1. Gateway Meter X Screen
Meter X has a CT for each conductor, with the following voltage references:
  • CT 1: L1
  • CT 2: L2
  1. For each CT, select the appropriate location representing what it is measuring:
    Informational PurposesAn informational icon, calling your attention
    Note
    Meter X CTs can only be configured as a single location, e.g. all CTs are Site.
    • Site: Used when CTs are installed on conductors (both L1 and L2) to measure Site.
    • Conductor: Used when CTs are installed (on both L1 and L2 conductors) to measure conductors being controlled by Conductor Limits.
      • Set the Conductor Limit in the Advanced Settings menu.
    • None: Used when the Meter X CTs are not being used.
    Informational PurposesAn informational icon, calling your attention
    Note
    If any of the CT readings are inverted and it has been confirmed that they are oriented correctly, select the Flip check box to correct the reading.
  2. Review the vitals for each CT (voltage, current, and power factor) to confirm they have been installed and configured correctly.
    Informational PurposesAn informational icon, calling your attention
    Note
    The live power flow and current readings are available for each CT in real time, as well as an overview of all meters and CT settings, in the Metering tab.